How level peak can be removed on E&H Radar wave level transmitter during filling of a silo.?

user-image
Question ajoutée par Junaid Iqbal , Instrumentation and Control Engineer in Ibrahim Fibers , Ibrahim Fibers Limited Polyester Plant
Date de publication: 2014/03/03
Junaid Iqbal
par Junaid Iqbal , Instrumentation and Control Engineer in Ibrahim Fibers , Ibrahim Fibers Limited Polyester Plant

It is actually the inherent problem in E&H Radar LT's. So be calm until they give solutions to remove this problem.

Ahmed Alam Khan Bangash
par Ahmed Alam Khan Bangash , Senior Manager Electrical & Instrumentation, Reliability Centered Maintenance at (Cement and Power) , MAPLE LEAF CEMENT FACTORY AND POWER PLANT

Dear one can find the damping option in E+H level trnasmitter and make sure during filling material should not come directly in direction of sensor. (in otherwords, Sensor placement is much more important.)

Ram Bala...
par Ram Bala... , E & I Supervisor , Renergy Engineering

Is it guided wave radar, some power obstruct at antana. so, check approximate level and manual maping of remain value of level (suppression) updating while level peak can removed.