Communiquez avec les autres et partagez vos connaissances professionnelles

Inscrivez-vous ou connectez-vous pour rejoindre votre communauté professionnelle.

Suivre

How to calculate ESP (External Static Pressure) for fresh and exhaust air fans ?

user-image
Question ajoutée par Ahmed Hussein Mohamed , MEP Building Maintenance Engineer , Emirates Post Group
Date de publication: 2014/03/08
Muhammad Arsalan Siddiqui
par Muhammad Arsalan Siddiqui , Associate Director (MEP) , JLL

Find which path is the longest and critical and as per the velocity in ducts measure the friction losses in ducts, bends etc. Add the static drops around air outlets like diffusers, grilles filters, dampers and add them all together.

Please remember to take10 or15% Factor of safety as the static or original basis are based on new system and with time the system becomes inefficient and due to dirt in filters and grilles air outets etc the drops becomes more so keep some factor other than you calculated to be on safe side.

Hope this will works

Jayakrishnan V G
par Jayakrishnan V G , Project Engineer , Future World Electromechanical LLC

Calculate the total pressure loss occuring in the line (Frictional loses in duct + Dynamic loses at fittings + Velocity Pressure required at outlet + Loses at terminals). Theoratically the ESP should be equal to this total pressure loss for effective selection of fan, but in actual consider a factor of safety and then determine the ESP. If there are branches calculate each branch starting from the begining of main line and determine which line has the largest pressure loss occuring, this line is the the critical line. The critical line pressure drop should be the basis of determining the ESP.

Abdul Mubeen  Mohammed
par Abdul Mubeen Mohammed , IT Support Engineer , Tech Mahindra - Other Locations

Total Dynamic head loss +10% factor of safety is considered as External static pressure.

In esp main purpose to select the fan capacity for example: |:::::::::::::::::::::::| if the duct have starting duct to bottom of the the flow pass through same at bottom of duct are we have to calculate the inside of the loss ex : friction loss,transition,Tee mean ,Tee branch,fire damber ,vcd,vav all losses has to be calculate..

Salman Sarang
par Salman Sarang , Design Manager - Mechanical Engineering , Cenomi Centers

ESP for blower fans & TDH for pumps are the terms associated with the capability of the device (Blower fan or Pump) to give desired result at the terminal point of the farthest or high resistance path. ESP depends majorly on duct material, duct construction, velocity, standard fittings & auxillary fittings, if any. ESP shall be appropriately estimated with safety factor to furnish alongwith the other fan selection data to the vendor.

Tajuddin  Shaik
par Tajuddin Shaik , Senior Sales Engineer , Metalex Gen. Trading Co.

Find the critical path for the machine u want to calculate esp then add up the lengths of straight ducts and check the fittings, etc., we will get the answer in wg.1 inch of wg =50Pa 

More Questions Like This