Why we start motors at the bigging with star connection and after that we use delta connection?

user-image
Question ajoutée par Sina shahabi , Maintenance of electrical installations , Islamic Republic of Iran Broadcasting VP Social Media
Date de publication: 2014/04/13
BONEY VARGHESE
par BONEY VARGHESE , Operations & Maintenance Manager , ALS Logistic Solutions

During starting the torque requirment is very high and the starting current will be very high. A Star-Delta starter is used for starting motors to reduce the starting current. In star connection only phase voltage (0.707 X Line voltage) comes across each winding. hence during starting the current is lesser compared to applying Line votage across a winding. So you need a power supply source of lesser current capacity to start the motor while using Star-Delta starter than when using a direct on line DOL starter. But after starting, your motor needs to take load and for meeting the torque requirment, Delta is needed. Thats why these Y-D starters chage over to delta connection once sufficient speed is reached.